BS 7671 Chapter 41 — Protection Against Electric Shock (Exam Prep)

Chapter 41 is the single most-tested chapter in the 18th Edition exam — Automatic Disconnection of Supply (ADS), maximum Zs values, RCD requirements, and the protective measures hierarchy. This guide is for electricians studying for the 18th Edition exam — Chapter 41 deep-dive.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 2,600+ UK electricians

11 min readUpdated 2026-10-24Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What does Chapter 41 cover in the 18th Edition exam?

Protection against electric shock: automatic disconnection of supply, maximum disconnection times (0.4 s TN and 0.2 s TT for final circuits up to 63 A with sockets), the maximum Zs Tables 41.2 to 41.5, RCD additional protection under Regulations 411.3.3 and 411.3.4, and the other protective measures such as double insulation, electrical separation and SELV.

2,600+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01ADS (Automatic Disconnection of Supply) under Section 411 is the primary protective measure for most installations.
  2. 02Disconnection times: 0.4s for final circuits up to 63A with sockets (32A fixed equipment) on TN system, 0.2s on TT system. 5s for distribution circuits..
  3. 03Maximum Zs values are in Tables 41.3 (for protective devices in BS EN 60898 / BS EN 61009) — memorise the common ones.
  4. 04Section 415 covers additional protection — 30mA RCDs for sockets up to 32A, supplementary equipotential bonding in special locations.
  5. 05Section 411.3.3 — RCD additional protection for socket circuits (the famous "30mA RCD" rule).
  6. 06A4:2026 lists no main changes to Chapter 41 — its PNB (protective neutral bonding) addition is in Regulation 312.2.1.1, Chapter 31. Regulation 411.3.3 was last redrafted at A2:2022.

01 · Exam Prep

The ADS Hierarchy

Chapter 41 establishes a protective hierarchy: (1) Basic protection — preventing contact with live parts (insulation, barriers). (2) Fault protection via ADS — disconnecting fault current within the required time. (3) Additional protection — 30mA RCD as a final safety net. Most exam questions test the ADS calculations. Memorise: Ohm’s Law applied to the fault circuit: I_fault = U_o / Z_fault, where Z_fault = R_phase + R_neutral + R_cpc (or Z_e + R_1 + R_2 in measurement terms).

Free download · PDF

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Exam Prep

Disconnection Times by Earthing System

Table 41.1 (Regulation 411.3.2.2) applies to final circuits rated up to 63 A with one or more socket-outlets, and up to 32 A supplying only fixed equipment: 0.4 s in a 230 V TN system and 0.2 s in a 230 V TT system. Distribution circuits and larger final circuits are allowed 5 s in TN systems (Regulation 411.3.2.3) and 1 s in TT systems (Regulation 411.3.2.4). Where an RCD provides fault protection, the Zs limits in Table 41.5 can be used (Regulation 411.4.204).

03 · Exam Prep

Maximum Zs Tables (41.3, 41.4, 41.5)

Table 41.2: fuses (BS 88-2, BS 88-3, BS 3036, BS 1362) for 0.4 s. Table 41.3: circuit-breakers to BS EN 60898 and the overcurrent part of RCBOs, Types B, C and D. Table 41.4: fuses for 5 s. Table 41.5: maximum Zs where an RCD provides fault protection, for example 1,667 Ω for a 30 mA RCD (50 V ÷ IΔn). Learn the Type B values: 6 A 7.28 Ω, 16 A 2.73 Ω, 32 A 1.37 Ω.

04 · Exam Prep

Section 415 — Additional Protection

Additional protection by a 30 mA RCD (Regulation 415.1.1) is required for socket-outlets up to 32 A (Regulation 411.3.3, with a documented risk-assessment exception outside dwellings), mobile equipment up to 32 A used outdoors, AC final circuits supplying luminaires in dwellings (Regulation 411.3.4), and in many Part 7 special locations. Separately, Regulation 421.1.7 in Chapter 42 has required AFDDs on single-phase socket-outlet circuits up to 32 A in HMOs, care homes, purpose-built student accommodation and high rise residential buildings since A2:2022.

In the app

Practise with unlimited mock exams

AI-generated mocks, instant marking, and explanations on every question — targeted at your weakest topics. From £6.99/mo.

Download on the App StoreGet it on Google Play

06 · Exam Prep

Typical Exam Questions on Chapter 41

"A 32 A Type B circuit-breaker protects a radial with a measured Zs of 1.2 Ω at room temperature. Does it comply?" Table 41.3 gives 1.37 Ω at operating temperature; a cold reading is compared with 80% of that, 1.10 Ω, so 1.2 Ω fails the check. "What is the maximum disconnection time for a 32 A socket circuit on a 230 V TT system?" 0.2 s. "Which socket-outlets need 30 mA additional protection?" Those rated up to 32 A, under Regulation 411.3.3.

07 · Exam Prep

Use Elec-Mate to Track and Study

Elec-Mate is built for UK electrical apprentices, qualified electricians, and business owners. Unit revision, AM2 mocks, OJT tracking, quoting, certification — all in one place. 7-day free trial.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from electricians and apprentices

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Start Free with Elec-Mate

Revision, AM2 practice, certificates and quoting in one app. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists