BS 7671 Chapter 43 — Overcurrent Protection (Exam Prep)

Chapter 43 covers overcurrent protection — protective device selection, discrimination, cable adiabatic. The second-most-tested chapter after 41. This guide is for electricians studying for the 18th Edition exam — Chapter 43 deep-dive.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 2,600+ UK electricians

11 min readUpdated 2026-10-24Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What does Chapter 43 cover in the 18th Edition exam?

Protection against overcurrent: the overload rule Ib ≤ In ≤ Iz with I2 ≤ 1.45 Iz (Regulation 433.1.1), fault current protection and breaking capacity (Section 434), and the adiabatic equation S = √(I²t) ÷ k for conductor sizes under fault conditions.

2,600+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Overload rule (Regulation 433.1.1): Ib ≤ In ≤ Iz, design current not more than the device rating, device rating not more than the cable’s current-carrying capacity, and I2 ≤ 1.45 Iz.
  2. 02Section 433 covers overload protection and Section 434 fault current (short-circuit) protection.
  3. 03The adiabatic equation S = √(I²t) ÷ k gives the minimum conductor size for the fault energy let through.
  4. 04Circuit-breaker Types B (3 to 5 × In), C (5 to 10 × In) and D (10 to 20 × In) are chosen by load inrush, and each has its own maximum Zs.
  5. 05Selectivity (discrimination): the device nearest the fault should operate first, checked with manufacturer data or time-current curves.

01 · Exam Prep

Protective Device Selection (Section 433)

The overload rule in Regulation 433.1.1 is Ib ≤ In ≤ Iz: the device rating In must be at least the design current Ib and no more than the cable’s current-carrying capacity Iz after rating factors, and the current I2 that operates the device must not exceed 1.45 Iz. Circuit-breakers to BS EN 60898 and BS 88 fuses meet the I2 condition automatically; a BS 3036 rewirable fuse needs an extra factor of 0.725. Type B suits resistive and general loads, Type C moderate inrush, and Type D high inrush such as transformers.

Free download · PDF

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Exam Prep

Discrimination Between Devices

Critical when you have downstream devices feeding circuits. The upstream device must NOT operate when a downstream device clears a fault. Discrimination is achieved by: time-current characteristics (slower upstream device), current rating (substantially higher upstream), or specific manufacturer charts. The exam often shows a one-line diagram and asks "is discrimination achieved between the 32A Type B downstream and the 100A Type B upstream?" Look up the time-current curves.

03 · Exam Prep

Adiabatic Equation for Short-Circuit

For fault current, the conductor must withstand the energy let through before the device clears: S ≥ √(I²t) ÷ k, where I is the fault current, t the operating time and k a factor for the conductor and insulation (115 for copper with 70 °C thermoplastic insulation; protective conductor k values are in Tables 54.2 to 54.5). For circuit-breakers the manufacturer’s I²t let-through is usually far lower than I² × t using a time read off the curve.

04 · Exam Prep

Fuses vs MCBs vs RCBOs

BS 88-2 fuses: industrial and commercial distribution, high breaking capacity. BS 88-3 fuses: the cartridge fuses in older domestic and small commercial boards (formerly BS 1361). BS EN 60898 circuit-breakers: resettable, typically 6 kA or 10 kA. BS EN 61009 RCBOs: circuit-breaker plus RCD in one device. A typical answer for a 32 A kitchen radial in a new board is a 32 A Type B RCBO, Type A for the RCD part.

In the app

Practise with unlimited mock exams

AI-generated mocks, instant marking, and explanations on every question — targeted at your weakest topics. From £6.99/mo.

Download on the App StoreGet it on Google Play

05 · Exam Prep

A4:2026 Changes to Chapter 43

Chapter 43 is not among the main changes listed in the A4:2026 introduction, so expect the same core principles. The A4 changes you are more likely to be asked about are elsewhere: PNB in Regulation 312.2.1.1, Table 52.1 for cables in walls, Section 545 and Chapter 57.

06 · Exam Prep

Typical Exam Questions on Chapter 43

"A circuit has a prospective fault current of 1.5 kA and the device clears in 0.1 s. What is the minimum protective conductor size, with k = 115?" S = √(1,500² × 0.1) ÷ 115 = 4.12 mm², so 4 mm² is too small and the next standard size, 6 mm², is needed. Using the circuit-breaker’s published I²t let-through instead usually gives a much smaller answer. "Type B or Type C for a motor with a high starting current?" Type C, checking that Zs still meets Table 41.3 for Type C.

07 · Exam Prep

Use Elec-Mate to Track and Study

Elec-Mate is built for UK electrical apprentices, qualified electricians, and business owners. Unit revision, AM2 mocks, OJT tracking, quoting, certification — all in one place. 7-day free trial.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from electricians and apprentices

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Start Free with Elec-Mate

Revision, AM2 practice, certificates and quoting in one app. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists