When does it apply? Reg 421.1.7 covers single-phase AC final circuits supplying socket-outlets up to 32 A. A cooker-only circuit is outside it; where the cooker control unit (CCU) includes an integral 13A socket-outlet, the circuit supplies a socket and the recommendation (or, in the premises listed, the requirement) applies.
What does an AFDD do? It detects the high-frequency signature of series and parallel arc faults — the type of fault that a standard MCB or RCD cannot detect because the fault current may be below the trip threshold. Arcing faults in appliance flexes and wiring are a leading cause of electrical fires.
Practical installation note: AFDDs are available as combined AFDD/RCBO modules for most consumer unit formats. On a new installation or full rewire, fitting an AFDD/RCBO on the cooker circuit adds minimal cost and goes beyond the Reg 421.1.7 recommendation. On an EICR, the absence of an AFDD on a cooker circuit is not itself a Code 2 defect, but the recommendation should be noted.