EICR observation codes are the classification system used to categorise defects, deficiencies, and departures from BS 7671 found during a periodic inspection and testing of an electrical installation. Every issue identified during the inspection is recorded in the observations table of the Electrical Installation Condition Report and assigned one of four classification codes.
The codes are defined in BS 7671:2018+A4:2026 and are explained in detail in IET Guidance Note 3: Inspection and Testing (GN3), which is the normative reference for code definitions. GN3 Table 3.5 sets out the explanation of C1, C2, C3, and FI and shall be consulted for code assignment (GN3). Note also that GN3 recognises a fifth outcome — an unlabelled "observation" — for items that do not require a code at all; this is distinct from C3, which does require an improvement to be recommended. The codes serve a critical purpose: they communicate the severity of each defect to the person responsible for the installation (the client, landlord, or building owner) and determine the overall assessment of the installation — Satisfactory or Unsatisfactory.
Getting the codes right matters. Under-classifying a dangerous defect as C3 instead of C2 could leave occupants at risk. Over-classifying a non-dangerous departure as C2 creates unnecessary alarm and undermines the credibility of the report. The four codes are:
C3
Improvement Recommended
The four codes at a glance
| Code | Meaning | Action required | Overall assessment |
|---|
| C1 | Danger present — risk of injury exists now | Immediate action; make safe before leaving site | Unsatisfactory |
| C2 | Potentially dangerous — risk of injury could arise | Urgent remedial action | Unsatisfactory |
| C3 | Improvement recommended — non-compliant but not dangerous | Advisory; remediation optional | Satisfactory |
| FI | Further investigation — could not be fully assessed | Investigate without delay | Unsatisfactory |