Building Management Systems (BMS) Mock Exam
Free building management systems mock exam. 30 questions from a 210-question bank covering BMS fundamentals, hardware and field wiring, HVAC integration including air handling units, fan coil units and chiller sequencing, lighting and access control, communication protocols, dashboards and analytics, and commissioning and handover.
- Questions
- 30
- Time limit
- 35 min
- Pass mark
- 70% · 21/30
- Question bank
- 210
Free, no sign-up. Retake as many times as you like — different questions each time.
Sample questions
01Which of these sits at the automation level of a BMS?
- AA web interface that staff use to change the schedules
- BA plant controller running the boiler house strategy
- CA pressure switch fitted across an AHU filter bank
- DA current relay fitted inside a fan motor starter
Why: The automation level is where decisions are made: the outstations and plant controllers that read inputs, run the strategy and drive outputs. The current relay and the filter pressure switch touch the plant, so they are field devices. The web interface is tempting because it is where settings change, but it is the management level: it sends settings down, it does not do the controlling.
02The BMS sends a varying speed reference to the drive on a supply fan. What type of point is that?
- AAn analogue input from the drive
- BAn analogue output to the drive
- CA digital output to the drive
- DA digital input from the drive
Why: A varying command sent out from the BMS is an analogue output, in the same family as a valve or damper position. A digital output is tempting because it also goes out to the plant, but it is only an on/off command such as start or enable. Inputs come into the BMS from the plant, not the other way.
03A packaged chiller has its own controller that is not on the BMS network. The BMS enables it from a digital output and reads a fault contact. The facilities manager wants its refrigerant pressures on the graphics. What is the position?
- AThe fault contact can be rescaled in the outstation to show each pressure
- BThe BMS only sees what is wired to it, so those values are not available
- CThe values already sit in the outstation and just need adding to the graphic
- DThe head end can poll the chiller controller for them over the BMS network
Why: A stand-alone controller is not on the BMS network, so the BMS only gets the enable it sends and the status or fault signals wired back; it does not see inside the plant. Polling over the network is tempting, but the chiller is not on that network. A fault contact is an on/off digital input and cannot carry a varying value.
Common questions
Is the Building Management Systems mock exam free?
Yes, it is free with no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.
Can I retake the mock exam?
Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.
Does this count as a qualification?
No. This is independent practice material and does not award a qualification, card or certificate. Where a subject has a formal qualification or card, you gain it through an approved provider.