Jump to the free three-phase volt drop calculator
VD = (mV/A/m3ph × Ib × L) / 1000
VD = line-to-line voltage drop in volts
mV/A/m3ph = three-phase millivolts per ampere per metre, from the BS 7671 Appendix 4 tables
Ib = design current per phase in amperes
L = run length in metres
Two things separate this from the single-phase calculation. You must read the three-phase column of the table rather than the single-phase column, and the answer is compared against a percentage of 400 V rather than 230 V.
Appendix 4, Section 6 is explicit about what the tabulated number already contains: for three-phase circuits the tabulated mV/A/m values relate to the line voltage, and balanced conditions have been assumed. The root 3 is inside the figure. Multiply the length by the design current, divide by 1000, and you have the line-to-line drop in volts.
The textbook formula with √3
Working from conductor resistance and reactance rather than the tables, the line-to-line drop on a balanced three-phase circuit is:
VD = √3 × I × L × (R cosφ + X sinφ)
√3 ≈ 1.732, converting the per-phase drop to a line-to-line drop
R, X = resistance and reactance of one conductor in ohms per metre
cosφ = load power factor (sinφ follows from it)
For a resistive load (cosφ = 1) it reduces to VD = √3 × I × R × L. The BS 7671 three-phase mV/A/m values are this same calculation done for you at the conductor operating temperature, which is why you never multiply a tabulated three-phase value by √3 again.
Cables above 16 mm²: resistance and reactance
For conductors of 16 mm² or less, Appendix 4, Section 6 says the inductance can be ignored and only a single mV/A/m value is tabulated. Above 16 mm² the table gives an impedance value (mV/A/m)z together with a resistive component (mV/A/m)r and a reactive component (mV/A/m)x. Using the impedance value on its own is safe but pessimistic.
Where the load power factor is worth taking into account, Section 6.2 gives the design value as cos φ × (mV/A/m)r + sin φ × (mV/A/m)x. This is the same relationship as the first-principles form √3 × I × L × (R cos φ + X sin φ), with the √3 and the per-metre resistance folded into the tabulated values. It matters most on three-phase motor circuits, where the power factor can be well below unity.
Frequency range (BS 7671 Appendix 4, Section 6)
The tabulated voltage drop values apply, for a.c. operation, to frequencies in the range 49 to 61 Hz. Appendix 4 warns that the voltage drop for cables operating at higher frequencies may be substantially greater. On the output side of a variable-frequency drive, the tabulated values are not the right tool.
In the app
Three-Phase Volt Drop Calculator (BS 7671)
Enter cable size, current and length to check volt drop against the 3% and 5% limits.