BS 7671 frequently references IP2X and IPXXB as minimum requirements for protection against direct contact with live parts. These two designations are related but not identical:
IP2X means solid objects of 12.5 mm and larger cannot enter, and the jointed test finger cannot reach live parts. The "2" is the first digit, referring to solid object protection. The "X" means the second digit (liquid protection) is not specified — it could be anything from 0 upwards.
IPXXB uses the additional letter "B" from BS EN 60529, which covers access only: the jointed test finger (12 mm diameter, 80 mm long) cannot reach live parts, even though the opening may be bigger than 12.5 mm. It is used where an enclosure has larger openings that are still finger-safe, such as the gaps around devices in a board.
Regulation 416.2.1 is why a board must have blanks in every spare way and why a missing blank is a standard EICR finding: the open way breaks the IPXXB enclosure. If an existing board does not meet IP2X/IPXXB, this is recorded as an observation during an EICR inspection.
Bathrooms have their own minimums under Regulation 701.512.2: IPX7 in zone 0, IPX4 in zones 1 and 2, and IPX5 where water jets are used for cleaning. The EIC certificate records the IP rating of equipment installed in special locations.