Sample questions

  1. 01A residential survey puts the new maximum demand at 85 A per phase, so you apply through ENA Connect Direct. How long does the DNO have to confirm?
    • A28 days, as for connect and notify
    • B5 working days from the application
    • C3 months, under its licence timescales
    • D10 working days from the application

    Why: For residential properties with a new maximum demand between 60 A and 100 A inclusive, the installer applies before installing and the network operator confirms within 10 working days. The 28 days is the window to notify after a connect-and-notify job. Licence timescales apply to applications above 100 A.

  2. 02A charge point at a house will only ever take power from the grid. Which network route covers telling the DNO about it?
    • AA G99 application, made before any of the work starts
    • BThe ENA process for EV charge points and heat pumps
    • CA building notice, sent to the local building control
    • DA G98 notification, as you would for a small generator

    Why: A charge point that only imports is a load, and goes through the ENA EV charge point and heat pump process: connect and notify within 28 days, or apply first. G98 and G99 are for generation, which only comes in if something exports, such as vehicle-to-grid. Building control deals with the Building Regulations, not the network.

  3. 03Which of these is one of the criteria a domestic job must meet to use the ENA connect-and-notify route?
    • AThe rating of the DNO cut-out is known
    • BThe charge point output is no more than 3.7 kW
    • CThe customer has an approved grant in place
    • DThe property already has a smart meter fitted

    Why: Section B of the form includes: only one additional piece of equipment, DNO cut-out rating known, no concerns over the DNO equipment, not a looped service, a metered supply, maximum demand below the cut-out rating and within 13.8 kVA per phase, and an AC output. A smart meter, a grant or a small output are not criteria.

Common questions

Is the Additional requirements mock exam free?

Yes, it is free with no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.

Can I retake the mock exam?

Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.

Does this count as a qualification?

No. This is independent practice material and does not award a qualification, card or certificate. Where a subject has a formal qualification or card, you gain it through an approved provider.

Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists