Free mock exam
EV Charging Installation Mock Exam
Free EV charging mock exam — ideal practice for the City & Guilds 2921-34 EV charging qualification (which replaced the 2921-31 in 2024) and other EV installer courses. 30 questions from a 210-question bank covering charging modes and connectors, the Smart Charge Points Regulations, circuit design and volt drop, RCD and DC fault protection, PME and the 722.411.4.1 options, earth electrodes, load management, testing and certification to BS 7671, and the OZEV grant rules.
- Questions
- 30
- Time limit
- 35 min
- Pass mark
- 70% · 21/30
- Question bank
- 391
Free, no sign-up. Retake as many times as you like — different questions each time.
Sample questions
01A customer calls the new 7 kW wall unit on their drive "the charger". Which of these is one of the jobs that unit actually does on AC?
- AIt turns the AC supply into DC before it reaches the car
- BIt stores energy so the car can charge faster at peak times
- CIt raises the supply voltage so the battery fills more quickly
- DIt tells the car the most current it is allowed to draw
Why: In Mode 3 the control pilot function extends to control equipment in the charge point (BS 7671 Part 2, Mode 3 charging), and that is how the unit tells the car the current it may draw. On AC the conversion to DC happens in the car; only Mode 4, which uses an off-board charger, converts outside the car. A wall unit does not store energy or raise the voltage.
02A balanced three-phase charge point draws 32 A in each line on a 400 V supply. A colleague works out its power as 400 × 32 and gets 12.8 kW. Roughly what is the real figure?
- A22 kW
- B38 kW
- C12.8 kW
- D7.4 kW
Why: For a balanced three-phase load P = √3 × U × I, so 1.732 × 400 × 32 = 22,170 W, about 22 kW, the same as 3 × 230 V × 32 A. The colleague’s 12.8 kW leaves out √3. 38 kW comes from multiplying 400 V by three, and 7.4 kW is one phase at 32 A.
03A 22 kW three-phase charge point is fed at 400 V. What line current should the design use for it?
- AAbout 55 A
- BAbout 32 A
- CAbout 18 A
- DAbout 96 A
Why: I = P ÷ (√3 × U) = 22,000 ÷ (1.732 × 400) = 31.8 A, so about 32 A in each line. 55 A comes from dividing by 400 V alone, 96 A from putting the whole 22 kW on one 230 V phase, and 18 A from dividing by 3 × 400 V.
Common questions
Is the EV Charging Installation mock exam free?
Yes, it is free with no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.
Can I retake the mock exam?
Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.
Does this count as a qualification?
No. This is independent practice material and does not award a qualification, card or certificate. Where a subject has a formal qualification or card, you gain it through an approved provider.